HI-943500B Conductivity Controller (High Range @ 19.99 mS/cm)
In Stock 1 Item available
HI-943500B
HI-943500 are panel-mounted conductivity controllers designed for simplicity of use in a wide range of industrial process applications. Four different models are available with different measurement ranges, to satisfy any application requirements.
The controller allows the direct connection of a potentiometric conductivity probe (HI 7638) with a cable up to 20 meters long, without using any transmitter.
- Automatic temperature compensation ensures fast, accurately compensated readings even during sudden temperature fluctuations
- Four different models are available with different measurement ranges
- Displays values on the easy to read LCD with backlighting
Four different models are available with different measurement ranges, to satisfy any application requirements.
The output configuration for connecting a recorder or a PLC can be chosen between 0-20 or 4-20 mA.
The LED on the front panel indicates the operating status of the controller.
The automatic temperature compensation (ATC) is performed directly by the HI-7638 probe with built-in temperature sensor.
The front panel is protected behind a transparent splash-proof cover.
Order Information:
The HI-943500 series is supplied with mounting brackets and instructions.
- HI-943500A: 0.0 to 199.9 mS/cm
- HI-943500B: 0.00 to 19.99 mS/cm
- HI-943500C: 0 to 1999 µS/cm
- HI-943500D: 0.0 to 199.9 µS/cm
Range | 0.0 to 19.99 mS/cm | |
Resolution | 0.01 mS/cm | |
Accuracy | ±2% F.S. | |
Temperature Compensation | automatic, 0 to 60°C (32 to 140°F), with ß=2%/°C | |
Recorder Output | 4-20 mA (isolated) | |
Setpoint Relay | 1, isolated, 2A, Max. 240 V, resistive load, 1,000,000 strokes | |
Alarm Relay | 1, isolated, 2A, Max. 240 V, resistive load, 1,000,000 strokes | |
Power Supply | 115/230 ±10% Vac; 50/60 Hz | |
Enclosure | black anodised aluminium body; front and back with ABS; transparent splash-proof front cover |
|
Environment | -10 to 50°C (4 to 122°F); RH max 95% non condensing | |
Panel Cutout | 141 x 69 mm (5.6 x 2.7") | |
Weight | 1 kg (2.2 lb.) |
Read More
Range | 0.0 to 19.99 mS/cm | |
Resolution | 0.01 mS/cm | |
Accuracy | ±2% F.S. | |
Temperature Compensation | automatic, 0 to 60°C (32 to 140°F), with ß=2%/°C | |
Recorder Output | 4-20 mA (isolated) | |
Setpoint Relay | 1, isolated, 2A, Max. 240 V, resistive load, 1,000,000 strokes | |
Alarm Relay | 1, isolated, 2A, Max. 240 V, resistive load, 1,000,000 strokes | |
Power Supply | 115/230 ±10% Vac; 50/60 Hz | |
Enclosure | black anodised aluminium body; front and back with ABS; transparent splash-proof front cover | |
Environment | -10 to 50°C (4 to 122°F); RH max 95% non condensing | |
Panel Cutout | 141 x 69 mm (5.6 x 2.7") | |
Weight | 1 kg (2.2 lb.) |